Sample test report

This is an example of the digital test records and asset register supplied after testing. All customer, site and asset details below are fictional.

ADVARO Test & Tag logo

ADVARO

Test & Tag

58 Bungle Bungle Crescent, Harrison ACT 2914

0494 816 871 · info@advaro.com.au

www.advaro.com.au

Prepared for

Sample Business Pty Ltd

Attn: A. Sample

12 Example Street, Canberra ACT 2600

Report number
ADV-SAMPLE-0002
Tested on
14 March 2026
Standard
AS/NZS 3760:2022
Items tested
12
Passed
10
Failed
2
Item IDEquipmentLocationClassVisualElectrical testResultTestedNext dueNotes
ADV-0001Desktop computer — power leadLevel 1 — Workstation 4Class IPassEarth continuity 0.09 Ω · Insulation >100 MΩPASS14/03/202614/03/2027—
ADV-0002LED monitorLevel 1 — Workstation 4Class IIPassInsulation >100 MΩPASS14/03/202614/03/2027—
ADV-0003Extension lead — 5 mLevel 1 — Meeting roomClass IFailNot tested — removed from serviceFAIL14/03/2026—Outer sheath damaged near plug. Removed from service and tagged out. Replacement recommended.
ADV-0004Power board — 6 outlet, overload protectedLevel 1 — Workstation 7Class IPassEarth continuity 0.11 Ω · Insulation >100 MΩPASS14/03/202614/03/2027—
ADV-0005Electric kettleLevel 1 — Staff kitchenClass IPassEarth continuity 0.07 Ω · Leakage 0.31 mAPASS14/03/202614/09/2026Kitchen environment — 6 month retest interval applied.
ADV-0006Microwave ovenLevel 1 — Staff kitchenClass IPassEarth continuity 0.12 Ω · Leakage 0.44 mAPASS14/03/202614/09/2026—
ADV-0007Laptop power supplyLevel 2 — Workstation 11Class IIPassInsulation >100 MΩPASS14/03/202614/03/2027—
ADV-0008Multifunction printerLevel 2 — Print areaClass IPassEarth continuity 0.10 Ω · Insulation >100 MΩPASS14/03/202614/03/2027—
ADV-0009Vacuum cleanerLevel 2 — Cleaner's storeClass IFailEarth continuity 2.4 Ω — outside limitFAIL14/03/2026—Failed earth continuity. Removed from service and tagged out. Referred to a licensed electrician.
ADV-0010Portable RCD leadLevel 2 — Maintenance storeClass IPassPush-button pass · Trip time 24 msPASS14/03/202614/09/2026—
ADV-0011Battery charger — cordless toolsLevel 2 — Maintenance storeClass IIPassInsulation >100 MΩPASS14/03/202614/09/2026—
ADV-0012Bar fridgeLevel 2 — Break-out areaClass IPassEarth continuity 0.08 Ω · Leakage 0.22 mAPASS14/03/202614/03/2027—

Testing carried out in accordance with AS/NZS 3760:2022. Items that failed inspection or testing have been clearly identified and removed from service as appropriate. Electrical repairs are referred to a licensed electrician — ADVARO Test & Tag does not carry out electrical repair work.

Sample document — fictional data, not a record of any real testing